Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
DIN rail (top hat rail) mounting optional
No
Overload release current setting
640.0 - 1600A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Suitable for DIN rail (top hat rail) mounting
No
Motor drive optional
Yes
Integrated earth fault protection
Yes
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Yes
Motor drive integrated
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
From same serie
1SDA070889R1 | E1.2N 1600 EKIP HI-TOUCH LSIG 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
DIN rail (top hat rail) mounting optional
Overload release current setting
640.0 .. 1600A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Integrated earth fault protection
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Motor drive integrated
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
From same serie
We use cookies to enhance your experience.