Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1250A
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Overload release current setting
500.0 - 1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Number of poles
3
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Back side
With switched-off indicator
Yes
Integrated earth fault protection
No
Motor drive optional
Yes
Motor drive integrated
No
With under voltage release
No
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA070848R1 | E1.2N 1250 EKIP HI-TOUCH LSI 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1250A
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Overload release current setting
500.0 .. 1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Number of poles
3
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Back side
With switched-off indicator
Integrated earth fault protection
Motor drive optional
Motor drive integrated
With under voltage release
Degree of protection (IP)
IP30
Complete device with protection unit
From same serie