Aleta.hr
Main Product Image

1SDA070696R1 | E1.2N 250 EKIP TOUCH LSIG 3P F F

Code: 1613772

ManufacturerRAZNO
Catalog number1SDA070696R1
Type
EAN code8015644745462

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

250A

Adjustment range undelayed short-circuit release

375.0 - 3750A

Integrated earth fault protection

Yes

Adjustment range short-term delayed short-circuit release

150.0 - 2500A

Position of connection for main current circuit

Back side

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Degree of protection (IP)

IP30

DIN rail (top hat rail) mounting optional

No

Overload release current setting

100.0 - 250A

Number of auxiliary contacts as normally open contact

0

Rated voltage

690 - 690V

Motor drive optional

Yes

Complete device with protection unit

Yes

Type of control element

Push button

Motor drive integrated

No

With switched-off indicator

Yes

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

66kA

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

No

Device construction

Built-in device fixed built-in technique


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA070696R1 | E1.2N 250 EKIP TOUCH LSIG 3P F F

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

250A

Adjustment range undelayed short-circuit release

375.0 .. 3750A

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

150.0 .. 2500A

Position of connection for main current circuit

Back side

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Degree of protection (IP)

IP30

DIN rail (top hat rail) mounting optional

Overload release current setting

100.0 .. 250A

Number of auxiliary contacts as normally open contact

0

Rated voltage

690 .. 690V

Motor drive optional

Complete device with protection unit

Type of control element

Push button

Motor drive integrated

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

66kA

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique