

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated permanent current Iu
3200A
Rated voltage
1000 - 1000V
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Type of control element
Push button
Number of poles
4
Motor drive optional
Yes
Motor drive integrated
No
Complete device with protection unit
Yes
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Overload release current setting
1280.0 - 3200A
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
From same serie
1SDA064654R1 | E4S/F 3200 PR122/DC IN=3200A 4P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated permanent current Iu
3200A
Rated voltage
1000 .. 1000V
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Type of control element
Push button
Number of poles
4
Motor drive optional
Motor drive integrated
Complete device with protection unit
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Overload release current setting
1280.0 .. 3200A
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
From same serie
We use cookies to enhance your experience.