Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
1000A
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Yes
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Motor drive integrated
No
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Adjustment range short-term delayed short-circuit release
600.0 - 600.0A
Overload release current setting
400.0 - 1000A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive optional
Yes
From same serie
1SDA059334R1 | E2S 1000 PR123/P-LSIG IN=1000A 3P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
1000A
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Motor drive integrated
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Adjustment range short-term delayed short-circuit release
600.0 .. 600.0A
Overload release current setting
400.0 .. 1000A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive optional
From same serie