Technical specifications
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Integrated earth fault protection
Yes
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Overload release current setting
400.0 - 1000A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
No
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Motor drive optional
Yes
From same serie
1SDA059222R1 | E1N 1000 PR121/P-LSIG IN=1000A 3P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Overload release current setting
400.0 .. 1000A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Degree of protection (IP)
IP30