Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
600.0 - 600.0A
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Back side
Rated voltage
690 - 690V
With under voltage release
No
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
With switched-off indicator
Yes
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Complete device with protection unit
Yes
Motor drive optional
Yes
Overload release current setting
400.0 - 1000A
Degree of protection (IP)
IP30
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA059203R1 | E1B 1000 PR123/P-LSIG IN=1000A 4

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
600.0 .. 600.0A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Back side
Rated voltage
690 .. 690V
With under voltage release
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
With switched-off indicator
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Complete device with protection unit
Motor drive optional
Overload release current setting
400.0 .. 1000A
Degree of protection (IP)
IP30
From same serie