Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
320.0 - 800A
Integrated earth fault protection
No
With under voltage release
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
Adjustment range short-term delayed short-circuit release
800 - 8000A
Position of connection for main current circuit
Back side
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
Motor drive integrated
No
Device construction
Built-in device fixed built-in technique
Number of poles
3
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Rated voltage
690 - 690V
With switched-off indicator
Yes
Motor drive optional
Yes
Adjustment range undelayed short-circuit release
1200.0 - 12000A
From same serie
1SDA058283R1 | E2S 800 PR121/P-LSI IN=800A 3P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
320.0 .. 800A
Integrated earth fault protection
With under voltage release
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Adjustment range short-term delayed short-circuit release
800 .. 8000A
Position of connection for main current circuit
Back side
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Motor drive integrated
Device construction
Built-in device fixed built-in technique
Number of poles
3
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Degree of protection (IP)
IP30
Rated voltage
690 .. 690V
With switched-off indicator
Motor drive optional
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
From same serie