Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
6300A
Adjustment range short-term delayed short-circuit release
3780.0 - 3780.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2520.0 - 6300A
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
Yes
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Complete device with protection unit
Yes
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
With switched-off indicator
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA057159R1 | E6V 6300 PR123/P-LSIG IN=6300A 3

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
6300A
Adjustment range short-term delayed short-circuit release
3780.0 .. 3780.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2520.0 .. 6300A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Complete device with protection unit
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Motor drive optional
With switched-off indicator