Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2000.0 - 5000A
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
5000A
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Adjustment range short-term delayed short-circuit release
5000 - 50000A
Motor drive integrated
No
Number of poles
3
Motor drive optional
Yes
With switched-off indicator
Yes
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
From same serie
1SDA057104R1 | E6V 5000 PR121/P-LI IN=5000A 3P F H

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2000.0 .. 5000A
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
5000A
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Adjustment range short-term delayed short-circuit release
5000 .. 50000A
Motor drive integrated
Number of poles
3
Motor drive optional
With switched-off indicator
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side