Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
6300A
Overload release current setting
2520.0 - 6300A
Integrated earth fault protection
No
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Device construction
Built-in device fixed built-in technique
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
6300 - 63000A
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button
With under voltage release
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
Motor drive integrated
No
With switched-off indicator
Yes
From same serie
1SDA057016R1 | E6H 6300 PR121/P-LI IN=6300A 4P F H

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
6300A
Overload release current setting
2520.0 .. 6300A
Integrated earth fault protection
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Device construction
Built-in device fixed built-in technique
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
6300 .. 63000A
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button
With under voltage release
Degree of protection (IP)
IP30
Motor drive optional
Motor drive integrated
With switched-off indicator
From same serie