Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
5000A
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Overload release current setting
2000.0 - 5000A
Motor drive optional
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
5000 - 50000A
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Type of control element
Push button
Integrated earth fault protection
No
Complete device with protection unit
Yes
With switched-off indicator
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
With under voltage release
No
Position of connection for main current circuit
Connection at separate chassis part
Type of electrical connection of main circuit
Connection at separate chassis part
From same serie
1SDA057001R1 | E6H 5000 PR121/P-LSI IN=5000A 4P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
5000A
Rated voltage
690 .. 690V
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Overload release current setting
2000.0 .. 5000A
Motor drive optional
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
5000 .. 50000A
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Type of control element
Push button
Integrated earth fault protection
Complete device with protection unit
With switched-off indicator
Degree of protection (IP)
IP30
Motor drive integrated
With under voltage release
Position of connection for main current circuit
Connection at separate chassis part
Type of electrical connection of main circuit
Connection at separate chassis part
From same serie