Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
3200 - 32000A
Overload release current setting
1280.0 - 3200A
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Type of control element
Push button
With switched-off indicator
Yes
Complete device with protection unit
Yes
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
From same serie
1SDA056882R1 | E4V 3200 PR121/P-LSIG IN=3200A 3P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
3200 .. 32000A
Overload release current setting
1280.0 .. 3200A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Type of control element
Push button
With switched-off indicator
Complete device with protection unit
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
From same serie