Technical specifications
Rated permanent current Iu
4000A
Overload release current setting
1600.0 - 4000A
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
4000 - 40000A
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
6000.0 - 60000A
With switched-off indicator
Yes
Number of poles
3
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Rated voltage
690 - 690V
From same serie
1SDA056801R1 | E4S 4000 PR121/P-LSI IN=4000A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
4000A
Overload release current setting
1600.0 .. 4000A
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
4000 .. 40000A
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
With switched-off indicator
Number of poles
3
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Degree of protection (IP)
IP30
Motor drive optional
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Rated voltage
690 .. 690V
From same serie