Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
1280.0 - 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Adjustment range short-term delayed short-circuit release
1920.0 - 1920.0A
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive optional
Yes
Type of control element
Push button
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
From same serie
1SDA056716R1 | E3V 3200 PR122/P-LSI IN=3200A 4P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
1280.0 .. 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Adjustment range short-term delayed short-circuit release
1920.0 .. 1920.0A
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive optional
Type of control element
Push button
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0