Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
1500.0 - 1500.0A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Rated permanent current Iu
2500A
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Number of poles
4
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Type of control element
Push button
Motor drive integrated
No
Motor drive optional
Yes
Overload release current setting
1000.0 - 2500A
From same serie
1SDA056684R1 | E3V 2500 PR122/P-LSI IN=2500A 4P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
1500.0 .. 1500.0A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Rated permanent current Iu
2500A
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Number of poles
4
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Complete device with protection unit
Type of control element
Push button
Motor drive integrated
Motor drive optional
Overload release current setting
1000.0 .. 2500A
From same serie