Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2000A
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Rated voltage
690 - 690V
Overload release current setting
800.0 - 2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
No
Adjustment range short-term delayed short-circuit release
1200.0 - 1200.0A
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Number of poles
4
With under voltage release
No
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Type of control element
Push button
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
From same serie
1SDA056655R1 | E3V 2000 PR123/P-LSIG IN=2000A 4P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2000A
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Rated voltage
690 .. 690V
Overload release current setting
800.0 .. 2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
Adjustment range short-term delayed short-circuit release
1200.0 .. 1200.0A
With switched-off indicator
DIN rail (top hat rail) mounting optional
Number of poles
4
With under voltage release
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Type of control element
Push button
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
From same serie