Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
1250 - 12500A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Integrated earth fault protection
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Rated permanent current Iu
1250A
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Overload release current setting
500.0 - 1250A
Number of poles
3
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA056577R1 | E3V 1250 PR121/P-LSI IN=1250A 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
1250 .. 12500A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Rated permanent current Iu
1250A
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Overload release current setting
500.0 .. 1250A
Number of poles
3
From same serie