Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
3200A
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Number of poles
3
Device construction
Built-in device slide-in technique (withdrawable)
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
With switched-off indicator
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Motor drive integrated
No
Overload release current setting
1280.0 - 3200A
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Yes
Adjustment range short-term delayed short-circuit release
3200 - 32000A
From same serie
1SDA056514R1 | E3H 3200 PR121/P-LSIG IN=3200A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
3200A
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Number of poles
3
Device construction
Built-in device slide-in technique (withdrawable)
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
With switched-off indicator
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Motor drive integrated
Overload release current setting
1280.0 .. 3200A
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Adjustment range short-term delayed short-circuit release
3200 .. 32000A
From same serie