Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
3200 - 32000A
Overload release current setting
1280.0 - 3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Rated voltage
690 - 690V
Rated permanent current Iu
3200A
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Yes
Motor drive optional
Yes
Integrated earth fault protection
No
DIN rail (top hat rail) mounting optional
No
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
With switched-off indicator
Yes
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
From same serie
1SDA056513R1 | E3H 3200 PR121/P-LSI IN=3200A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
3200 .. 32000A
Overload release current setting
1280.0 .. 3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Rated voltage
690 .. 690V
Rated permanent current Iu
3200A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Motor drive optional
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
With switched-off indicator
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
From same serie