Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
640.0 - 1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Type of control element
Push button
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
With switched-off indicator
Yes
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA056405R1 | E3H 1600 PR122/P-LSIG IN=1600A 3

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
640.0 .. 1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Type of control element
Push button
Position of connection for main current circuit
Back side
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Motor drive optional
From same serie