Technical specifications
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Rated permanent current Iu
800A
Rated voltage
690 - 690V
With under voltage release
No
Adjustment range short-term delayed short-circuit release
800 - 8000A
Degree of protection (IP)
IP30
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Number of poles
3
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
No
Overload release current setting
320.0 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA056353R1 | E3H 800 PR121/P-LSI IN=800A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Rated permanent current Iu
800A
Rated voltage
690 .. 690V
With under voltage release
Adjustment range short-term delayed short-circuit release
800 .. 8000A
Degree of protection (IP)
IP30
Type of control element
Push button
Complete device with protection unit
Motor drive integrated
Motor drive optional
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of poles
3
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Overload release current setting
320.0 .. 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting