Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
1280.0 - 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Adjustment range short-term delayed short-circuit release
1920.0 - 1920.0A
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive optional
Yes
Motor drive integrated
No
Position of connection for main current circuit
Back side
Number of poles
3
With switched-off indicator
Yes
Degree of protection (IP)
IP30
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA056308R1 | E3S 3200 PR122/P-LSI IN=3200A 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
1280.0 .. 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Adjustment range short-term delayed short-circuit release
1920.0 .. 1920.0A
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive optional
Motor drive integrated
Position of connection for main current circuit
Back side
Number of poles
3
With switched-off indicator
Degree of protection (IP)
IP30
From same serie