Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
1500.0 - 1500.0A
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Yes
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Overload release current setting
1000.0 - 2500A
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
No
Number of poles
4
Degree of protection (IP)
IP30
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Complete device with protection unit
Yes
From same serie
1SDA056300R1 | E3S 2500 PR122/P-LSI IN=2500A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated voltage
690 .. 690V
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
1500.0 .. 1500.0A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Overload release current setting
1000.0 .. 2500A
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
Number of poles
4
Degree of protection (IP)
IP30
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Complete device with protection unit
From same serie