Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
800.0 - 2000A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 - 690V
Rated permanent current Iu
2000A
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
2000 - 20000A
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Degree of protection (IP)
IP30
With switched-off indicator
Yes
Motor drive integrated
No
Type of control element
Push button
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA056242R1 | E3S 2000 PR121/P-LSIG IN=2000A 3

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
800.0 .. 2000A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 .. 690V
Rated permanent current Iu
2000A
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
2000 .. 20000A
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP30
With switched-off indicator
Motor drive integrated
Type of control element
Push button
Adjustment range undelayed short-circuit release
3000.0 .. 30000A