Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated voltage
690 - 690V
Rated permanent current Iu
1600A
Overload release current setting
640.0 - 1600A
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Yes
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
No
Motor drive optional
Yes
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
No
Position of connection for main current circuit
Connection at separate chassis part
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA056236R1 | E3S 1600 PR122/P-LSI IN=1600A 4P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated voltage
690 .. 690V
Rated permanent current Iu
1600A
Overload release current setting
640.0 .. 1600A
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Position of connection for main current circuit
Connection at separate chassis part
From same serie