Aleta.hr
Main Product Image

1SDA056229R1 | E3S 1600 PR122/P-LSIG IN=1600A 3P W

Code: 1592816

ManufacturerRAZNO
Catalog number1SDA056229R1
Type
EAN code8015644575694

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release

960.0 - 960.0A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

75kA

Rated voltage

690 - 690V

Rated permanent current Iu

1600A

With switched-off indicator

Yes

Suitable for DIN rail (top hat rail) mounting

No

Number of auxiliary contacts as normally closed contact

0

Motor drive integrated

No

DIN rail (top hat rail) mounting optional

No

Adjustment range undelayed short-circuit release

2400.0 - 24000A

Motor drive optional

Yes

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

640.0 - 1600A

Number of auxiliary contacts as normally open contact

0

Integrated earth fault protection

Yes

Complete device with protection unit

Yes

Device construction

Built-in device slide-in technique (withdrawable)

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Type of electrical connection of main circuit

Connection at separate chassis part

Number of poles

3

Type of control element

Push button


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA056229R1 | E3S 1600 PR122/P-LSIG IN=1600A 3P W

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release

960.0 .. 960.0A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

75kA

Rated voltage

690 .. 690V

Rated permanent current Iu

1600A

With switched-off indicator

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally closed contact

0

Motor drive integrated

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Motor drive optional

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

640.0 .. 1600A

Number of auxiliary contacts as normally open contact

0

Integrated earth fault protection

Complete device with protection unit

Device construction

Built-in device slide-in technique (withdrawable)

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Type of electrical connection of main circuit

Connection at separate chassis part

Number of poles

3

Type of control element

Push button