Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Rated voltage
690 - 690V
Overload release current setting
640.0 - 1600A
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Integrated earth fault protection
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
1600 - 16000A
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
3
From same serie
1SDA056224R1 | E3S 1600 PR121/P-LI IN=1600A 3P W M

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
Motor drive optional
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
3
From same serie