Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
640.0 - 1600A
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
With switched-off indicator
Yes
Type of control element
Push button
Motor drive integrated
No
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 - 690V
Motor drive optional
Yes
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated permanent current Iu
1600A
Integrated earth fault protection
Yes
From same serie
1SDA056221R1 | E3S 1600 PR122/P-LSIG IN=1600A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
640.0 .. 1600A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
With switched-off indicator
Type of control element
Push button
Motor drive integrated
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Motor drive optional
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated permanent current Iu
1600A
Integrated earth fault protection
From same serie