Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Integrated earth fault protection
Yes
Adjustment range short-term delayed short-circuit release
1920.0 - 1920.0A
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Number of poles
4
Overload release current setting
1280.0 - 3200A
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Yes
Rated voltage
690 - 690V
With under voltage release
No
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
From same serie
1SDA056173R1 | E3N 3200 PR122/P-LSIG IN=3200A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
1920.0 .. 1920.0A
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Number of poles
4
Overload release current setting
1280.0 .. 3200A
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Rated voltage
690 .. 690V
With under voltage release
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
Complete device with protection unit
From same serie