Technical specifications
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Integrated earth fault protection
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Adjustment range short-term delayed short-circuit release
1920.0 - 1920.0A
Number of auxiliary contacts as change-over contact
4
Rated permanent current Iu
3200A
Overload release current setting
1280.0 - 3200A
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Number of poles
4
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
Motor drive integrated
No
Rated voltage
690 - 690V
Position of connection for main current circuit
Back side
From same serie
1SDA056155R1 | E3N 3200 PR122/P-LI IN=3200A 4P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Adjustment range short-term delayed short-circuit release
1920.0 .. 1920.0A
Number of auxiliary contacts as change-over contact
4
Rated permanent current Iu
3200A
Overload release current setting
1280.0 .. 3200A
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
With switched-off indicator
Number of poles
4
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Motor drive integrated
Rated voltage
690 .. 690V
Position of connection for main current circuit
Back side
From same serie