Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 - 690V
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Overload release current setting
1000.0 - 2500A
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Motor drive integrated
No
Adjustment range undelayed short-circuit release
3750.0 - 37500A
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
With under voltage release
No
Number of poles
4
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive optional
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
1500.0 - 1500.0A
From same serie
1SDA056140R1 | E3N 2500 PR122/P-LSI IN=2500A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Overload release current setting
1000.0 .. 2500A
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Motor drive integrated
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
With under voltage release
Number of poles
4
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
1500.0 .. 1500.0A