Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
1600 - 16000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
With under voltage release
No
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Yes
Motor drive optional
Yes
Type of control element
Push button
Number of poles
3
Degree of protection (IP)
IP30
Rated voltage
690 - 690V
Motor drive integrated
No
Type of electrical connection of main circuit
Connection at separate chassis part
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA056097R1 | E2L 1600 PR121/P-LSI IN=1600A 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
With under voltage release
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Motor drive optional
Type of control element
Push button
Number of poles
3
Degree of protection (IP)
IP30
Rated voltage
690 .. 690V
Motor drive integrated
Type of electrical connection of main circuit
Connection at separate chassis part
From same serie