1SDA056066R1 | E2L 1250 PR121/P-LSIG IN=1250A 3
Code: 1592653
Sign in or create an account for lower prices and other benefits
Code: 1592653
Sign in or create an account for lower prices and other benefits
Technical specifications
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
Type of control element
Push button
Number of poles
3
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Adjustment range short-term delayed short-circuit release
1250 - 12500A
Overload release current setting
500.0 - 1250A
Complete device with protection unit
Yes
Motor drive integrated
No
Rated permanent current Iu
1250A
Zagreb:
0 pcs
Zadar:
0 pcs
1SDA056066R1 | E2L 1250 PR121/P-LSIG IN=1250A 3
Code
1592653
Catalog number
1SDA055840R1
Type
Power circuit-breaker for trafo/generator/installation protection
Manufacturer
ABBSerie
-
9.923,86 €
Total stock:
0 PCS
Built-in device slide-in technique (withdrawable)
130kA
1875.0 .. 18750A
0
Connection at separate chassis part
0
4
Connection at separate chassis part
IP30
Push button
3
690 .. 690V
1250 .. 12500A
500.0 .. 1250A
1250A