Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated voltage
690 - 690V
Overload release current setting
640.0 - 1600A
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Integrated earth fault protection
No
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
4
Number of auxiliary contacts as change-over contact
4
With under voltage release
No
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive optional
Yes
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
Degree of protection (IP)
IP30
Rated permanent current Iu
1600A
Position of connection for main current circuit
Back side
Motor drive integrated
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA055996R1 | E2S 1600 PR122/P-LSI IN=1600A 4P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Integrated earth fault protection
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Number of poles
4
Number of auxiliary contacts as change-over contact
4
With under voltage release
Type of control element
Push button
Complete device with protection unit
Motor drive optional
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Degree of protection (IP)
IP30
Rated permanent current Iu
1600A
Position of connection for main current circuit
Back side
Motor drive integrated
From same serie