Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
No
With under voltage release
No
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
Position of connection for main current circuit
Back side
DIN rail (top hat rail) mounting optional
No
Number of poles
3
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Overload release current setting
640.0 - 1600A
Complete device with protection unit
Yes
Motor drive optional
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA055987R1 | E2S 1600 PR122/P-LI IN=1600A 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
With under voltage release
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Position of connection for main current circuit
Back side
DIN rail (top hat rail) mounting optional
Number of poles
3
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Overload release current setting
640.0 .. 1600A
Complete device with protection unit
Motor drive optional
From same serie