Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
500.0 - 1250A
Device construction
Built-in device slide-in technique (withdrawable)
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
750.0 - 750.0A
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Yes
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Rated permanent current Iu
1250A
Type of control element
Push button
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Motor drive optional
Yes
From same serie
1SDA055981R1 | E2S 1250 PR122/P-LSIG IN=1250A 4P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
500.0 .. 1250A
Device construction
Built-in device slide-in technique (withdrawable)
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
750.0 .. 750.0A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Rated permanent current Iu
1250A
Type of control element
Push button
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
Motor drive optional
From same serie