Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
500.0 - 1250A
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
750.0 - 750.0A
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1875.0 - 18750A
With switched-off indicator
Yes
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
1250A
Motor drive integrated
No
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive optional
Yes
From same serie
1SDA055884R1 | E2N 1250 PR122/P-LSI IN=1250A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
500.0 .. 1250A
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
750.0 .. 750.0A
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
With switched-off indicator
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
1250A
Motor drive integrated
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive optional
From same serie