Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2000A
Integrated earth fault protection
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Rated voltage
690 - 690V
Number of auxiliary contacts as change-over contact
4
Overload release current setting
800.0 - 2000A
Adjustment range short-term delayed short-circuit release
1200.0 - 1200.0A
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Type of control element
Push button
Complete device with protection unit
Yes
With under voltage release
No
Number of poles
4
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive optional
Yes
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
Code: 1592439
1SDA055852R1 | E2B 2000 PR122/P-LSI IN=2000A 4P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
2000A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
4
Overload release current setting
800.0 .. 2000A
Adjustment range short-term delayed short-circuit release
1200.0 .. 1200.0A
With switched-off indicator
DIN rail (top hat rail) mounting optional
Motor drive integrated
Type of control element
Push button
Complete device with protection unit
With under voltage release
Number of poles
4
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive optional
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part