Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Rated permanent current Iu
1600A
Overload release current setting
640.0 - 1600A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 - 690V
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Adjustment range undelayed short-circuit release
2400.0 - 24000A
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Motor drive optional
Yes
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Motor drive integrated
No
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Number of auxiliary contacts as change-over contact
4
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA055820R1 | E2B 1600 PR122/P-LSI IN=1600A 4P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Rated permanent current Iu
1600A
Overload release current setting
640.0 .. 1600A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Motor drive optional
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Complete device with protection unit
Motor drive integrated
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Number of auxiliary contacts as change-over contact
4