Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated voltage
690 - 690V
Overload release current setting
640.0 - 1600A
Integrated earth fault protection
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
With under voltage release
No
Type of control element
Push button
With switched-off indicator
Yes
Number of poles
4
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA055772R1 | E1N 1600 PR122/P-LSI IN=1600A 4P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
With under voltage release
Type of control element
Push button
With switched-off indicator
Number of poles
4
Complete device with protection unit
Motor drive integrated
Motor drive optional
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30