Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Adjustment range short-term delayed short-circuit release
800 - 8000A
Overload release current setting
320.0 - 800A
Rated permanent current Iu
800A
Rated voltage
690 - 690V
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Complete device with protection unit
Yes
Integrated earth fault protection
No
Motor drive optional
Yes
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Degree of protection (IP)
IP30
With switched-off indicator
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA055696R1 | E1N 800 PR121/P-LI IN=800A 3P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Adjustment range short-term delayed short-circuit release
800 .. 8000A
Overload release current setting
320.0 .. 800A
Rated permanent current Iu
800A
Rated voltage
690 .. 690V
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Complete device with protection unit
Integrated earth fault protection
Motor drive optional
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Degree of protection (IP)
IP30
With switched-off indicator
From same serie