Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 - 690V
Overload release current setting
640.0 - 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Rated permanent current Iu
1600A
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Complete device with protection unit
Yes
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive integrated
No
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
From same serie
1SDA055685R1 | E1B 1600 PR122/P-LSIG IN=1600A 3P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Rated permanent current Iu
1600A
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Complete device with protection unit
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
DIN rail (top hat rail) mounting optional
With switched-off indicator
From same serie