Technical specifications
Rated voltage
690 - 690V
With switched-off indicator
Yes
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Device construction
Built-in device slide-in technique (withdrawable)
Rated permanent current Iu
800A
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
With under voltage release
No
Number of poles
3
Adjustment range short-term delayed short-circuit release
800 - 8000A
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Motor drive integrated
No
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Overload release current setting
320.0 - 800A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA055617R1 | E1B 800 PR121/P-LSI IN=800A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
With switched-off indicator
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Device construction
Built-in device slide-in technique (withdrawable)
Rated permanent current Iu
800A
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
With under voltage release
Number of poles
3
Adjustment range short-term delayed short-circuit release
800 .. 8000A
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
Motor drive optional
Motor drive integrated
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Overload release current setting
320.0 .. 800A
From same serie