Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
80kA
Adjustment range short-term delayed short-circuit release
4000 - 40000A
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
1600.0 - 4000A
Rated voltage
690 - 690V
Integrated earth fault protection
No
DIN rail (top hat rail) mounting optional
No
With under voltage release
No
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
6000.0 - 60000A
With switched-off indicator
Yes
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
4000A
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
From same serie
1SDA055544R1 | E4S/F 4000 PR121/P-LI IN=4000A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
80kA
Adjustment range short-term delayed short-circuit release
4000 .. 40000A
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
1600.0 .. 4000A
Rated voltage
690 .. 690V
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
With under voltage release
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
With switched-off indicator
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
4000A
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30
From same serie