Technical specifications
Rated permanent current Iu
4000A
Device construction
Built-in device slide-in technique (withdrawable)
Overload release current setting
1600.0 - 4000A
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
2400.0 - 2400.0A
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Complete device with protection unit
Yes
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Number of poles
4
With switched-off indicator
Yes
Motor drive optional
Yes
Integrated earth fault protection
Yes
Position of connection for main current circuit
Connection at separate chassis part
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA055533R1 | E4H/F 4000 PR122/P-LSIG IN=4000A

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
4000A
Device construction
Built-in device slide-in technique (withdrawable)
Overload release current setting
1600.0 .. 4000A
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
2400.0 .. 2400.0A
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Complete device with protection unit
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Number of poles
4
With switched-off indicator
Motor drive optional
Integrated earth fault protection
Position of connection for main current circuit
Connection at separate chassis part
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
From same serie