Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- EATON
Technical specifications
System configuration IT
No
System configuration TN-C-S
Yes
Nominal discharge surge current (8/20)
20kA
System configuration TN-S
Yes
System configuration DC
No
System configuration other
Yes
Nominal voltage DC
0V
Max. PV-voltage
0V
Max. overcurrent protection device, series connection (fuse)
125A
Max. continuous voltage DC
0V
Voltage protection level
1.4kV
System configuration TN
Yes
Leakage-current free
No
Integrated short-circuit protection
No
Max. overcurrent protection device, parallel connection (fuse)
0A
System configuration TT
No
Number of conductors (without earthing)
4
Integrated backup fuse
No
Nominal voltage AC
280V
Max. continuous voltage AC
280V
Voltage protection level N-PE
0kV
Integrated short-circuit protection selective to fuse gG
0A
Max. conductor cross section solid (solid, stranded)
25mm²
Construction size
4 modular spacing
Mounting method
DIN rail (top hat rail) 35 mm
Degree of protection (IP)
IP20
Signalling at the device
Optic
Max. discharge surge current (8/20)
40kA
Voltage protection level L-N
0kV
Short-circuit breaking capacity (Isccr)
0kA
Max. conductor cross section flexible (fine-strand)
35mm²
System configuration TN-C
No
Category type 2
Yes
With remote signalling contact
No
From same serie
SPCT2-280/4

Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- EATON
Technical specifications
System configuration IT
System configuration TN-C-S
Nominal discharge surge current (8/20)
20kA
System configuration TN-S
System configuration DC
System configuration other
Nominal voltage DC
0V
Max. PV-voltage
0V
Max. overcurrent protection device, series connection (fuse)
125A
Max. continuous voltage DC
0V
Voltage protection level
1.4kV
System configuration TN
Leakage-current free
Integrated short-circuit protection
Max. overcurrent protection device, parallel connection (fuse)
0A
System configuration TT
Number of conductors (without earthing)
4
Integrated backup fuse
Nominal voltage AC
280V
Max. continuous voltage AC
280V
Voltage protection level N-PE
0kV
Integrated short-circuit protection selective to fuse gG
0A
Max. conductor cross section solid (solid, stranded)
25mm²
Construction size
4 modular spacing
Mounting method
DIN rail (top hat rail) 35 mm
Degree of protection (IP)
IP20
Signalling at the device
Optic
Max. discharge surge current (8/20)
40kA
Voltage protection level L-N
0kV
Short-circuit breaking capacity (Isccr)
0kA
Max. conductor cross section flexible (fine-strand)
35mm²
System configuration TN-C
Category type 2
With remote signalling contact
From same serie