Technical specifications
Release characteristic
K
Rated voltage
230V
Number of protected poles
1
Number of poles (total)
1
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
10kA
Current limiting class
3
Suitable for flush-mounted installation
No
Rated impulse withstand voltage Uimp
4kV
Rated current
2A
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
6kA
Frequency
50 - 60Hz
Rated insulation voltage Ui
440V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
6kA
Voltage type
AC/DC
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 55°C
Connectable conductor cross section multi-wired
0 - 25mm²
Built-in depth
69mm
Additional equipment possible
Yes
Concurrently switching neutral conductor
No
Width in number of modular spacings
1
Pollution degree
2
Connectable conductor cross section solid-core
0 - 35mm²
Over voltage category
3
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
2CDS251001R0277 | S201-K2

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Release characteristic
K
Rated voltage
230V
Number of protected poles
1
Number of poles (total)
1
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
10kA
Current limiting class
3
Suitable for flush-mounted installation
Rated impulse withstand voltage Uimp
4kV
Rated current
2A
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
6kA
Frequency
50 .. 60Hz
Rated insulation voltage Ui
440V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
6kA
Voltage type
AC/DC
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 .. 55°C
Connectable conductor cross section multi-wired
0 .. 25mm²
Built-in depth
69mm
Additional equipment possible
Concurrently switching neutral conductor
Width in number of modular spacings
1
Pollution degree
2
Connectable conductor cross section solid-core
0 .. 35mm²
Over voltage category
3