Aleta.hr
Main Product Image

1SDA069611R1 | XT4S 160 Ekip E-LSIG In=40A 3p F

Code: 1531118

ManufacturerRAZNO
Catalog numberXT4S40E3
Type
EAN code8015644703479

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

220 - 690V

Rated permanent current Iu

160A

DIN rail (top hat rail) mounting optional

Yes

Number of poles

3

Suitable for DIN rail (top hat rail) mounting

No

With switched-off indicator

No

Integrated earth fault protection

No

Device construction

Built-in device fixed built-in technique

Complete device with protection unit

Yes

Type of electrical connection of main circuit

Bolt connection

Type of control element

Toggle

With under voltage release

No

Adjustment range undelayed short-circuit release

40 - 400A

Adjustment range short-term delayed short-circuit release

40 - 400A

Position of connection for main current circuit

Front side

Degree of protection (IP)

IP20

Motor drive optional

Yes

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Motor drive integrated

No

Overload release current setting

16.0 - 40A


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA069611R1 | XT4S 160 Ekip E-LSIG In=40A 3p F

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

220 .. 690V

Rated permanent current Iu

160A

DIN rail (top hat rail) mounting optional

Number of poles

3

Suitable for DIN rail (top hat rail) mounting

With switched-off indicator

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

Complete device with protection unit

Type of electrical connection of main circuit

Bolt connection

Type of control element

Toggle

With under voltage release

Adjustment range undelayed short-circuit release

40 .. 400A

Adjustment range short-term delayed short-circuit release

40 .. 400A

Position of connection for main current circuit

Front side

Degree of protection (IP)

IP20

Motor drive optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Motor drive integrated

Overload release current setting

16.0 .. 40A

From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.