Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Overload release current setting
320.0 - 800A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1000 - 10000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
With under voltage release
No
Integrated earth fault protection
No
Number of poles
4
Motor drive integrated
No
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Type of control element
Toggle
Motor drive optional
Yes
With switched-off indicator
No
Complete device with protection unit
Yes
Rated voltage
690 - 690V
From same serie
1SDA069432R1 | T6V 800 PR221DS-LS/I IN=800 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Overload release current setting
320.0 .. 800A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1000 .. 10000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With under voltage release
Integrated earth fault protection
Number of poles
4
Motor drive integrated
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Type of control element
Toggle
Motor drive optional
With switched-off indicator
Complete device with protection unit
Rated voltage
690 .. 690V